Draft ventilation motor DWG format

Pay with:
i agree with "Terms for Customers"
Sold: 0
Refunds: 0

Uploaded: 25.03.2010
Content: 00325181937030.____________________.rar (360,31 kB)

Description

1. GENERAL INFORMATION.
1.1. This project is designed on the basis of tasks and drawings of architectural and construction part.
1.2. The project solves the heating and ventilation of premises dealership.
1.3. In developing the project used:
- Architecture and planning assignment;
- SNIP 2.04.05-91 "HVAC";
- SNIP II-3-79 * "Building Heat Engineering".
1.4. The project provides for air heating system.
1.5. Ambient air temperature for calculation adopted in the winter period (par. B) -15 ° C in the summer (par. A) - +31.8 deg C.
1.6. The coolant in the heating system - water with a temperature of 80-60 degrees C.
1.7. The heat source is a modular boiler house, located in the yard. Fuel for the boiler is natural gas.
1.8. As the heaters, stoves with water heat exchanger. The tambour gateways installed air curtains, also with water heat exchanger.
1.9. Provision emptying the heating system for repair.
1.10. The project includes supply and exhaust ventilation system. Provided an organized system with mechanical drive. Installed air handling units (main, backup). For air-conditioning and heating of the supply air units are freon cooler and a heat exchanger for hot water.
1.11. Extract from the premises via the slotted grille.
1.12. Ducts made of galvanized steel with thickness of 0.55 mm. Provision insulation material supply air system "Penofol A" 4 mm thick.

Feedback

0
No feedback yet.
Period
1 month 3 months 12 months
0 0 0
0 0 0
In order to counter copyright infringement and property rights, we ask you to immediately inform us at support@plati.market the fact of such violations and to provide us with reliable information confirming your copyrights or rights of ownership. Email must contain your contact information (name, phone number, etc.)